CORTEXA
← Browse
arxiveess.SY2026-07-09

On the Convergence of the Current-Constrained Power Angle Curve of Virtual Admittance-Based Grid Forming Converters

Haoxiang Zong, Chen Zhang, Yu Zhang, Xu Cai, Marta Molinas

The current-constrained power-angle curve (PAC) is crucial for the transient synchronization stability (TSS) analysis of virtual admittance-based (VA) grid-forming (GFM) converters. Its formulation and application rely on the quasi-steady-state assumption critically, i.e., the active power can converge to its steady-state across the entire angle space in both a stable and fast manner. Despite this assumption is intuitively perceivable, it lack sufficient clarification, particularly on underlying behaviors if violated. To this end, this paper uncovers a new phenomenon on the non-uniform convergence of the VA-PAC. To achieve this, an eigen-sweep-based analysis of the full-order VA-PAC model with detailed controls is conducted, by which the existence of this issue is theoretically confirmed. On this basis, the open-loop stability and response-rate conditions of the full-order VA-PAC model for ensuring its convergence are clarified. Findings of this work can provide deeper insights into the existing TSS analyses of GFM converters, and are expected to provoke new analyses.

View free PDFSource page

Related papers

arxiveess.SY2026-07-09

A graph theoretic view on small signal stability of inverter-based power grids

Iva Bačić, Jakob Niehues, Philipp C. Böttcher, Cai Dieball, Leonardo Rydin Gorjão, Andrea Benigni, et al.

Dynamic grid stability is traditionally ensured with synchronous generators. Modern grids rely substantially more on inverter-based resources, which require grid-forming control to guarantee adequate system-wide synchronization and stability. Small-signal stability has granted va…

View free PDFSource page
arxiveess.SY2026-07-07

Structural Analysis and Internal Stability Enhancement of Virtual-Admittance-Based Cascaded GFMIs Under Unity Voltage-Feedback Decoupling

Stephen Arinze Obi, Ki-Hyun Kim, Jae-Jung Jung

Virtual admittance (VA) is widely used in cascaded voltage-control and current-control (VC-CC) grid-forming inverters (GFMIs) because it shapes the converter terminal behavior while preserving the current-regulation path required for current shaping and limiting. However, the ach…

View free PDFSource page
arxiveess.SY2026-07-10

Structural Decoupling and Current-Angle Steering for Post-Fault Recovery of Current-Limited Grid-Forming Inverters

Neethu Sajeev, Stephen Arinze Obi, Jae-Jung Jung

Reliable fault recovery of grid-forming (GFM) converters under current-limited conditions is increasingly important as inverter-based resources replace synchronous generation. Existing current-limiting strategies primarily focus on current-angle regulation and synchronization tra…

View free PDFSource page
arxiveess.SY2026-07-12

Open-Source Python Tool for Grid Converter Output Admittance Identification

Juho Määttä, Jarno Kukkola, Janne Seppänen, Marko Hinkkanen

Frequency-domain analysis based on converter output admittance is a key tool for studying converter-driven stability in power grids. This paper presents a Python-based identification tool built on a completely open-source simulator, eliminating the need for commercial licenses su…

View free PDFSource page
arxiveess.SY2026-07-14

Stability Analysis of Grid-Following and Grid-Forming Converters Connected to Generators

Alessandra Casiraghi, Marzio Barresi, Samuele Grillo

This work presents an examination of the main interactions between grid-following (GFL) and grid-forming (GFM) voltage source converters (VSCs) and synchronous generators (SGs), capturing the dynamics of a real power grid and pointing out the limitations of considering an ideal o…

View free PDFSource page
arxiveess.SY2026-06-27

Negative Resistance Caused by Intra-Loop Coupling in Virtual-Admittance-Based Grid-Forming Control

Jaekeun Lee, Minwoo Jeong, Jae-Jung Jung, Xiongfei Wang, Shenghui Cui

This paper addresses the harmonic instability problem of the virtual-admittance (VA)-based grid-forming control. It is revealed that the intra-loop coupling among the VA control, the inner-loop current control, and the voltage feedforward control results in an \(s^2\)-term in the…

View free PDFSource page